Dual-coil Valve Control
Two MVPs can drive a dual-coil valve with a signal of 0-5VDC, or 0-10VDC, or 4-20mA.
If enable switch is not used, set MVP #1 to be Mode 1, MVP #2 to be Mode 2.
If enable switch is used, set MVP #1 to be Mode 3, MVP #2 to be Mode 4.
Set 2.5-5VDC for MVP #1, 7.5-10VDC for MVP #2 when there is no deadband in the command input. Normally we
leave deadband in the middle and both ends.
Set the dither and output settings according to the valve specifications.